FM Approved Blast Rated Construction Exclusive Haz-Safe Buildings' Wall Design

Frame members, roofing and floor channels clad with 10 gauge wall, roof and floor plate are all continuously welded. Exposed 2" square x 1/4" thick tubular steel vertical members up to 8' high clad with 10 gauge steel plate have a 120 lbs. per square foot rating. FM approved and tested 4' wide x 8' long explosion relief panel has 30 ft. per square foot of clear opening.

Haz-Safe Building's proven approach to custom engineered pre-manufactured rooms, enclosures and buildings provide superior blast rated performance as well as practical operation and aesthetic considerations. Basic explosion resistant construction requires the following elements, some or all of which Haz-Safe can provides.

a. Two methods of blast rated construction techniques have Factory Mutual (FM) approval up to 16' tall, floor-to-ceiling. By combining methods, approval is available beyond 16' high. Haz-Safe Buildings are the only hazmat steel buildings manufactured with FM approval above 7'6" high.

b. N.F.P.A. 30, as interpreted by FM, requires pre-manufactured steel buildings to be blast rated up to 100 lbs. per square foot. Haz-Safe standard construction begins at 120 lbs. per square foot blast rating.

c. Some hazmat buildings are required to be protected with explosion relief capability. Haz-Safe provides a patented hinged 8' wide x 4' high relief panel that has been FM tested and approved. N.F.P.A. 30 requires 1 ft. per square foot of clear relief opening per every 50 cubic feet of volume.

NOTE: All U.L. listed and FM approved components and assembled explosion relief panels are not capable of being fire rated. All hazmat rooms and buildings equipped with explosion relief panels have compromised the fire rated wall(s) and ceiling(s). A rated wall of 1, 2 or 4 hours has in fact, with explosion relief panel(s), approximately 5 to 10 minutes before extreme heat from the chemical fire destroys the panel(s) and allows fresh oxygen into the space to feed the fire. Also, fire suppression systems are designed for the protected space to be sealed in order to put out the fire.

d. Blast relief may be substituted with patented sloped floors and trenches, low level posi-ventilation tubes within the sump elevated flooring connected to dual exhaust fans on emergency power grid or generation. Requires approval by local authority having jurisdiction.

e. When hazmat building is to be within 50' of another structure or facility on site, Haz-Safe has provided a patented blast shaft installed over relief panels to protect against the harmful venting of explosives.

f. Haz-Safe's blast rated wall construction is designed to be as thin as possible, thereby providing either more real estate outside or more usable floor space inside.